# HOLD-state overshoot from a disturbance: root cause and fix plan Investigation of the overshoot visible in `docs/overshoot.png`: a cold-water disturbance during a steady HOLD at 30°C caused `theta_ist` to overshoot to ~30.5°C and stay there, rather than settling back at soll. This document records the diagnosis and the (not yet implemented) fix plan. Numbers below are pulled from `logs/log_latest.json`. ## Incident summary - Steady HOLD at 30.0°C. Cold water added → `theta_ist` (Smith-corrected) dipped to ~29.49°C (`diff ≈ 0.51°C`). - `diff` never reached `Thresholds.HoldHeat` (1.0°C, `temp_controller_fsm.py`), so **the FSM never left `HOLD`** — the entire episode happened inside what the system still considered "holding". - `pid_hold` (outer loop, `Hold: {kp:0.6, ki:0, kd:0, kt:0}` — pure proportional) tracked `0.6 * max(0, diff)` exactly, tick for tick, peaking at `pid_hold_y ≈ 0.31` — nowhere near its `y_max=1.0` ceiling. Confirmed directly against logged samples: `rate_soll` == `0.6*diff` to the last digit throughout. - `pid_heat` (inner loop, `Heat: {kp:0.08, ki:0.02, kd:0, kt:1.5}`) then chased that `heatrate_soll` target, driving commanded power from a baseline ~500W burst-cycle up to **~2600W** (`y ≈ 0.74` of the 3500W max, see `tasks/heater.py:58-59`: `power = get_power_max() * y`). - Plant dead time (`Td=17s`) and thermal mass (`M=27.96 kg`, `C≈3403 J/(kg·K)`, from `PlantParams` in the log) meant heat from that burst kept arriving after `theta_ist` had already crossed back over soll. By the time `rate_soll` had fallen back to exactly `0` (outer loop asking for zero heat rate), `power_set` was still **1442 W**, decaying only gradually over the next ~35s (1193 → 979 → 817 → 632 → 487 → 337 → 142 W) rather than snapping to 0. - No active cooling actuator exists; the passive loss coefficient (`L=0.2 W/(kg·K)`) gives a time constant `C/L ≈ 17,000s (~4.7h)`, so the resulting ~0.4°C plateau above soll does not visibly decay within any reasonable observation window. **Root cause:** `pid_heat`'s integral term (`yi`) accumulated during the ~130s the outer loop demanded a real (if modest) heat rate, and nothing bounded that accumulation — the existing anti-windup in `Pid.process()` (`components/pid/pid.py:45-48`) is back-calculation that only corrects `yi` when the combined output `y` is actually clamped at `y_min`/`y_max`. Since `y` peaked at ~0.74, well under the `1.0` ceiling, `awu` was `0` the entire time and the anti-windup mechanism never engaged. The integrator just had to unwind naturally against real (delayed) negative error, which took ~35+ seconds after the outer loop had already zeroed its target. ## Rejected approach: flat `yi_max` clamp on `pid_heat` The first fix considered was bounding `yi` directly (`self.yi = max(-yi_max, min(yi_max, self.yi))` in `Pid.process()`, independent of the existing `y`-clamp anti-windup). Numeric check against the real plant model kills this as a standalone fix: | scenario | P needed | y needed | |---|---|---| | 1.5 K/min ramp @ 30°C | 2435 W | 0.696 | | 1.5 K/min ramp @ 50°C | 2547 W | 0.728 | | 1.5 K/min ramp @ 66°C | 2636 W | 0.753 | | the actual HOLD disturbance (peak) | 2600 W | 0.74 | At steady state (`err=0`), `kp*err` contributes nothing — the entire `y≈0.7-0.75` needed to sustain a genuine 1.5 K/min ramp has to come from `yi` alone, for as long as the ramp lasts. That's the *same* range the disturbance transient itself peaked at. So: - `yi_max` set low enough to meaningfully shorten the observed hangover (well under ~0.74, e.g. ~0.3) would permanently cap a real 1.5 K/min ramp far below its commanded rate — not a transient dip, a persistent, uncorrectable shortfall for the entire ramp. - `yi_max` set high enough not to interfere with legitimate ramps (~0.75+) sits at or above what the incident already peaked at, so it never engages and does nothing for the hangover. A flat magnitude clamp cannot distinguish "leftover integral from an already-resolved disturbance" from "integral correctly holding up a real ongoing ramp" — in this plant they occupy the same output range. **Rejected.** ## Refined plan: gate `pid_heat` by FSM state instead Bound (or freeze) the *rate* at which `pid_heat` reacts based on FSM state, not a constant on `yi`, since real sustained-rate demand only ever happens in `HEAT`; in `HOLD` any large `yi` is by definition windup, since the target rate there is always ~0 outside of a real disturbance. 1. **New flag `heat_loop_active`**, scoped to `HOLD` only, in `TempControllerFsm`. `is_holding()` stays `state == HOLD` regardless — Sud step "have we reached target" logic is unaffected. 2. **While `heat_loop_active` is False in `HOLD`:** force `y=0`, skip `pid_heat.process()` entirely (freeze it, don't reset — same bumpless-resume convention already used for `HOLD→HEAT`, see `temp_controller_fsm.py:99-101`). `pid_hold` keeps running every tick regardless (it's pure-P, no windup risk, and its output is needed to evaluate the engage condition below). 3. **Engagement (`False→True`)**, checked each tick while in `HOLD`: - Explicit command — a new `engage_heat_loop()`/`force_heat()` call, wired to a manual UI action and/or auto-fired from `set_theta_soll()` when the new target is a genuine change (not the same value re-sent every tick). - `diff >= Thresholds.HoldHeatEngage` (new config key). 4. **Disengagement:** once `diff` settles back inside the existing `HoldHeat`/`HoldCool` band, held for a short dwell time (a few seconds), to avoid chatter right at the boundary. 5. **Config/back-compat:** new threshold merges into `DEFAULT_THRESHOLDS` the same way existing ones do (`temp_controller_base.py:30`). ### Open design question (unresolved) `HoldHeatEngage` needs to sit **below** the existing `HoldHeat`/`HeatHold` FSM threshold (currently `1.0°C`) to ever fire from inside `HOLD` — if `HoldHeat` stays at `1.0`, the FSM fully escalates to `HEAT` (where `pid_heat` always runs anyway) before any larger engage threshold is ever reached. Two ways to resolve, not yet decided: - Raise `HoldHeat`/`HeatHold` too, widening the HOLD↔HEAT band so `HOLD` covers the full deadband and the new flag is the only gate within it. - Keep `HoldHeat` at `1.0`, set the engage threshold below it (e.g. ~0.7-0.8°C) — loop only goes offline for small disturbances, engaging before the FSM would escalate to full `HEAT` anyway. ## Test plan (not yet implemented) Stdlib `unittest`, no pytest — `tests/components/pid/test_pid.py`, discoverable via `python -m unittest discover -t . -s tests/components/pid`. **A. Unit-level, isolated `Pid`** — no plant involved. Feed a synthetic `err` sequence shaped like the incident (positive `heatrate_err ≈ 0.3` held for ~130 ticks, then decaying/negative tail, matching the real `rate_soll - rate_ist` pulled from the log) into `pid_heat` with the loop gated (frozen while "HOLD"/inactive) vs ungated (today's behavior). Assert: recovery time (ticks after error goes negative until `y` drops back under a small threshold) is measurably shorter when gated; `yi` never grows during the frozen window. **B. Closed-loop, self-contained synthetic scenario** — no dependency on the multi-MB log file. Real numbers from `PlantParams`/`config.json`: `Pot(dt)` with `M=27.96, C=3403.43, L=0.2, Td=17`, ambient from `config.json`; `TempController` via `PidFactory.create('Smith', dt)` with the real `Hold`/`Heat`/`Cool` gains. Run closed-loop (controller's own `y` drives the plant, unlike `utils/replay_sim.py`'s open-loop observe-only mode): hold at 30°C until settled, knock `plant.temp` down ~0.5°C to emulate the cold-water event, keep ticking for several minutes. Run twice — gating on vs off — and assert peak overshoot above 30.0°C is measurably smaller with gating, while a separate run driving a genuine 1.5 K/min ramp confirms gating does *not* reduce the sustained ramp rate (guards against reintroducing the flat-clamp regression above). ## Status Plan only — nothing in this document has been implemented yet.