Extract FSM logic from TempControllerBase into TempControllerFsm

States, DEFAULT_THRESHOLDS, the three PIDs, FSM state vars, process_fsm(),
on_state_entered(), set_enabled(), and is_holding() move to a new
TempControllerFsm class in temp_controller_fsm.py. TempControllerBase
inherits from both APid and TempControllerFsm; States is re-exported so
existing imports in temp_controller_smith.py are unaffected.

Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Tqxrk8uj4M3w3d3eXm3xK8
This commit is contained in:
2026-06-25 20:50:20 +02:00
co-authored by Claude Sonnet 4.6
parent f7355270c8
commit 42d7776a85
2 changed files with 229 additions and 219 deletions
+104 -219
View File
@@ -1,245 +1,130 @@
from components import APid
from components.pid.pid import Pid
import enum
from components.pid.temp_controller_fsm import TempControllerFsm, States, DEFAULT_THRESHOLDS
DEFAULT_THRESHOLDS = {
"HoldHeat": 1.0,
# HoldCool used to be 0.1 ("eagerly give up and coast" made sense back
# when COOL meant nothing more than going idle - it's an active state
# with its own PID now, so a threshold this tight relative to a real
# heater's discrete power steps/sensor noise causes the system to
# chatter in and out of it every tick, resetting both pid_hold's and
# pid_cool's integrators each time and never letting either actually
# converge. Symmetric with the others instead.
"HoldCool": 1.0,
"HeatHold": 1.0,
"HeatCool": 1.0,
"CoolHold": 1.0,
"CoolHeat": 1.0,
}
class States(enum.Enum):
INIT = -1,
IDLE = 0,
HEAT = 1,
HOLD = 2,
COOL = 3
class TempControllerBase(APid, TempControllerFsm):
class TempControllerBase(APid):
def __init__(self, dt):
APid.__init__(self)
TempControllerFsm.__init__(self, dt)
self.theta_ist_set = 0
self.theta_soll_set = 0
self.heatrate_ist_set = 0
self.heatrate_soll_set = 1.0
self.heatrate_soll = 1.0
self.theta_ist = 0
self.heatrate_ist = 0
# None until set_params() is called - mirrors Pid's own
# params/set_params() (components/pid/pid.py), whose process()
# already relies on the same "None means not configured yet".
self.params = None
self.y = -1
def __init__(self, dt):
APid.__init__(self)
self.pid_hold = Pid(dt)
self.pid_heat = Pid(dt)
# Separate gains for ramping down (negative diff) - the actuator
# (e.g. a heat-only Pot/heater) is responsible for clamping the
# resulting negative power to whatever it's actually capable of;
# the controller itself no longer assumes "can't cool" == "must go
# idle".
self.pid_cool = Pid(dt)
self.theta_ist_set = 0
self.theta_soll_set = 0
self.heatrate_ist_set = 0
self.heatrate_soll_set = 1.0
self.heatrate_soll = 1.0
self.theta_ist = 0
self.heatrate_ist = 0
# None until set_params() is called - mirrors Pid's own
# params/set_params() (components/pid/pid.py), whose process()
# already relies on the same "None means not configured yet".
self.params = None
self.thresholds = None
self.y = -1
self.state = States.INIT
self.is_startup = True
# Master on/off switch: while disabled, the FSM is held in IDLE and
# the controller tries not to drive the heater at all (output
# forced to 0) - off by default, enabled either by the user
# (manual mode) or by SudTask for the duration of a run.
self.enabled = False
def set_params(self, params):
self.params = params
self.thresholds = {**DEFAULT_THRESHOLDS, **params.get('Thresholds', {})}
self.pid_hold.set_params(params['Hold'])
self.pid_heat.set_params(params['Heat'])
self.pid_cool.set_params(params['Cool'])
def set_params(self, params):
self.params = params
self.thresholds = {**DEFAULT_THRESHOLDS, **params.get('Thresholds', {})}
self.pid_hold.set_params(params['Hold'])
self.pid_heat.set_params(params['Heat'])
self.pid_cool.set_params(params['Cool'])
def _require_params(self):
"""Called by each subclass's process() before doing anything else -
without it, a missing set_params() call would otherwise only
surface as an unhelpful "'NoneType' object is not subscriptable"
buried inside Pid.process() (components/pid/pid.py), once
process_pid() below gets to it."""
if self.params is None:
raise RuntimeError(
"{}.process(): PID gains not set - call set_params() first".format(type(self).__name__))
def _require_params(self):
"""Called by each subclass's process() before doing anything else -
without it, a missing set_params() call would otherwise only
surface as an unhelpful "'NoneType' object is not subscriptable"
buried inside Pid.process() (components/pid/pid.py), once
process_pid() below gets to it."""
if self.params is None:
raise RuntimeError(
"{}.process(): PID gains not set - call set_params() first".format(type(self).__name__))
def is_configured(self):
"""Whether set_params() has been called - lets a caller (e.g.
TcTask's own process loop) check upfront and skip processing
gracefully while not yet configured, rather than relying on
process() raising. Overridden by TempController(Smith) to also
require its internal model's plant params/ambient."""
return self.params is not None
def is_configured(self):
"""Whether set_params() has been called - lets a caller (e.g.
TcTask's own process loop) check upfront and skip processing
gracefully while not yet configured, rather than relying on
process() raising. Overridden by TempController(Smith) to also
require its internal model's plant params/ambient."""
return self.params is not None
def post_pid(self):
pass
def on_state_entered(self, state):
pass
def set_ambient_temperature(self, theta_amb):
pass
def post_pid(self):
pass
def set_model_plant_params(self, model_params):
pass
def set_ambient_temperature(self, theta_amb):
pass
def set_model_power(self, power):
pass
def set_model_plant_params(self, model_params):
pass
def set_theta_ist(self, value):
self.theta_ist_set = value
if self.is_startup:
self.is_startup = False
def set_model_power(self, power):
pass
def get_theta_ist(self):
return self.theta_ist
def set_theta_ist(self, value):
self.theta_ist_set = value
if self.is_startup:
self.is_startup = False
def get_theta_ist_set(self):
"""The raw sensor reading, as last pushed via set_theta_ist() -
unlike get_theta_ist() (self.theta_ist), this is updated the
instant a reading comes in, regardless of whether process() has
ever actually run (e.g. before set_params()/a model-based
controller's plant params have been configured - see SudTask.
send_forecast(), which needs a real "current temperature" at the
moment a Sud is loaded, before this controller may have ticked
even once)."""
return self.theta_ist_set
def get_theta_ist(self):
return self.theta_ist
def set_heatrate_ist(self, value):
self.heatrate_ist_set = value
def get_theta_ist_set(self):
"""The raw sensor reading, as last pushed via set_theta_ist() -
unlike get_theta_ist() (self.theta_ist), this is updated the
instant a reading comes in, regardless of whether process() has
ever actually run (e.g. before set_params()/a model-based
controller's plant params have been configured - see SudTask.
send_forecast(), which needs a real "current temperature" at the
moment a Sud is loaded, before this controller may have ticked
even once)."""
return self.theta_ist_set
def get_heatrate_ist(self):
return self.heatrate_ist
def set_heatrate_ist(self, value):
self.heatrate_ist_set = value
def set_theta_soll(self, value):
self.theta_soll_set = value
# Recompute the FSM right away against the new target, rather than
# waiting for the next process() tick - otherwise self.state can
# still read HOLD from the previous target for up to one tick
# after a much-further-away one is pushed, which would make
# is_holding() report "reached" instantly instead of once the gap
# has actually closed.
self.process_fsm(self.theta_soll_set - self.theta_ist)
def get_heatrate_ist(self):
return self.heatrate_ist
def get_theta_soll(self):
return self.theta_soll
def set_theta_soll(self, value):
self.theta_soll_set = value
# Recompute the FSM right away against the new target, rather than
# waiting for the next process() tick - otherwise self.state can
# still read HOLD from the previous target for up to one tick
# after a much-further-away one is pushed, which would make
# is_holding() report "reached" instantly instead of once the gap
# has actually closed.
self.process_fsm(self.theta_soll_set - self.theta_ist)
def get_theta_soll_set(self):
return self.theta_soll_set
def get_theta_soll(self):
return self.theta_soll
def set_heatrate_soll(self, value):
self.heatrate_soll_set = value
def get_theta_soll_set(self):
return self.theta_soll_set
def get_heatrate_soll(self):
return self.heatrate_soll
def is_holding(self):
"""Whether the FSM currently considers theta_ist close enough to
theta_soll_set to no longer be actively heating/cooling toward
it - the single source of truth for "is a ramp toward the
current target done" (see tasks/sud.py's SudTask)."""
return self.state == States.HOLD
def get_heatrate_soll_set(self):
return self.heatrate_soll_set
def set_heatrate_soll(self, value):
self.heatrate_soll_set = value
def process_pid(self, theta_err, heatrate_err, hold_scale=1.0):
self.pid_hold.process(theta_err, -self.theta_ist, hold_scale)
def set_enabled(self, value):
self.enabled = value
# Only the PID actually driving y is advanced - otherwise the
# inactive one (e.g. pid_heat while COOL has pid_cool driving)
# would keep silently integrating against a heatrate_err that
# isn't actually under its control, building a stale windup that
# causes a discontinuity in y the moment it takes back over.
if self.state == States.IDLE:
self.y = 0
elif self.state == States.COOL:
self.pid_cool.process(heatrate_err, -self.heatrate_ist)
self.y = self.pid_cool.get_y()
else:
self.pid_heat.process(heatrate_err, -self.heatrate_ist)
self.y = self.pid_heat.get_y()
def get_heatrate_soll(self):
return self.heatrate_soll
self.post_pid()
def get_heatrate_soll_set(self):
return self.heatrate_soll_set
def process_fsm(self, diff):
state_next = self.state
if self.state == States.INIT:
# Wait for a real sensor reading before acting on anything,
# regardless of enabled - avoids reacting to the bogus
# theta_ist=0 default.
if not self.is_startup:
state_next = States.IDLE
elif not self.enabled:
state_next = States.IDLE
elif self.state == States.IDLE:
# Just (re-)enabled - resolve straight to HEAT/COOL/HOLD against
# the real gap, the same threshold check the HOLD branch below
# uses, rather than landing in HOLD and waiting for the next
# tick to correct it: is_holding() is read synchronously within
# this very same call chain (tasks/sud.py's SudTask.on_step_
# changed() pushes the new step's setpoint via set_theta_soll(),
# which calls this method directly), so an unconditional HOLD
# here gets mistaken for "ramp already reached" and can finish
# a freshly (re-)started step instantly - see SudTask.
# on_process()'s is_holding() check. pid_heat/pid_cool were
# frozen (see process_pid()) and possibly stale for as long as
# we were disabled - start whichever one matters clean rather
# than resuming wherever it last left off.
self.pid_hold.reset()
self.pid_heat.reset()
self.pid_cool.reset()
if diff >= self.thresholds['HoldHeat']:
state_next = States.HEAT
elif diff <= -self.thresholds['HoldCool']:
state_next = States.COOL
else:
state_next = States.HOLD
elif self.state == States.HOLD:
if diff >= self.thresholds['HoldHeat']:
state_next = States.HEAT
self.pid_heat.reset()
elif diff <= -self.thresholds['HoldCool']:
state_next = States.COOL
self.pid_cool.reset()
elif self.state == States.HEAT:
if diff <= -self.thresholds['HeatCool']:
state_next = States.COOL
self.pid_cool.reset()
elif diff <= self.thresholds['HeatHold']:
state_next = States.HOLD
self.pid_hold.reset()
elif self.state == States.COOL:
if diff >= self.thresholds['CoolHeat']:
state_next = States.HEAT
self.pid_heat.reset()
elif diff >= -self.thresholds['CoolHold']:
state_next = States.HOLD
self.pid_hold.reset()
# pid_heat was frozen during COOL (see process_pid()) -
# resume it clean rather than from whatever it last held
# before COOL took over, which by now may be a stale fit
# for a completely different part of the curve.
self.pid_heat.reset()
if state_next != self.state:
self.state = state_next
self.on_state_entered(state_next)
def process_pid(self, theta_err, heatrate_err, hold_scale=1.0):
self.pid_hold.process(theta_err, -self.theta_ist, hold_scale)
# Only the PID actually driving y is advanced - otherwise the
# inactive one (e.g. pid_heat while COOL has pid_cool driving)
# would keep silently integrating against a heatrate_err that
# isn't actually under its control, building a stale windup that
# causes a discontinuity in y the moment it takes back over.
if self.state == States.IDLE:
self.y = 0
elif self.state == States.COOL:
self.pid_cool.process(heatrate_err, -self.heatrate_ist)
self.y = self.pid_cool.get_y()
else:
self.pid_heat.process(heatrate_err, -self.heatrate_ist)
self.y = self.pid_heat.get_y()
self.post_pid()
def get_power(self):
return self.y
def get_power(self):
return self.y
+125
View File
@@ -0,0 +1,125 @@
import enum
from components.pid.pid import Pid
DEFAULT_THRESHOLDS = {
"HoldHeat": 1.0,
# HoldCool used to be 0.1 ("eagerly give up and coast" made sense back
# when COOL meant nothing more than going idle - it's an active state
# with its own PID now, so a threshold this tight relative to a real
# heater's discrete power steps/sensor noise causes the system to
# chatter in and out of it every tick, resetting both pid_hold's and
# pid_cool's integrators each time and never letting either actually
# converge. Symmetric with the others instead.
"HoldCool": 1.0,
"HeatHold": 1.0,
"HeatCool": 1.0,
"CoolHold": 1.0,
"CoolHeat": 1.0,
}
class States(enum.Enum):
INIT = -1,
IDLE = 0,
HEAT = 1,
HOLD = 2,
COOL = 3
class TempControllerFsm:
def __init__(self, dt):
self.pid_hold = Pid(dt)
self.pid_heat = Pid(dt)
# Separate gains for ramping down (negative diff) - the actuator
# (e.g. a heat-only Pot/heater) is responsible for clamping the
# resulting negative power to whatever it's actually capable of;
# the controller itself no longer assumes "can't cool" == "must go
# idle".
self.pid_cool = Pid(dt)
self.thresholds = None
self.state = States.INIT
self.is_startup = True
# Master on/off switch: while disabled, the FSM is held in IDLE and
# the controller tries not to drive the heater at all (output
# forced to 0) - off by default, enabled either by the user
# (manual mode) or by SudTask for the duration of a run.
self.enabled = False
def on_state_entered(self, state):
pass
def set_enabled(self, value):
self.enabled = value
def is_holding(self):
"""Whether the FSM currently considers theta_ist close enough to
theta_soll_set to no longer be actively heating/cooling toward
it - the single source of truth for "is a ramp toward the
current target done" (see tasks/sud.py's SudTask)."""
return self.state == States.HOLD
def process_fsm(self, diff):
state_next = self.state
if self.state == States.INIT:
# Wait for a real sensor reading before acting on anything,
# regardless of enabled - avoids reacting to the bogus
# theta_ist=0 default.
if not self.is_startup:
state_next = States.IDLE
elif not self.enabled:
state_next = States.IDLE
elif self.state == States.IDLE:
# Just (re-)enabled - resolve straight to HEAT/COOL/HOLD against
# the real gap, the same threshold check the HOLD branch below
# uses, rather than landing in HOLD and waiting for the next
# tick to correct it: is_holding() is read synchronously within
# this very same call chain (tasks/sud.py's SudTask.on_step_
# changed() pushes the new step's setpoint via set_theta_soll(),
# which calls this method directly), so an unconditional HOLD
# here gets mistaken for "ramp already reached" and can finish
# a freshly (re-)started step instantly - see SudTask.
# on_process()'s is_holding() check. pid_heat/pid_cool were
# frozen (see process_pid()) and possibly stale for as long as
# we were disabled - start whichever one matters clean rather
# than resuming wherever it last left off.
self.pid_hold.reset()
self.pid_heat.reset()
self.pid_cool.reset()
if diff >= self.thresholds['HoldHeat']:
state_next = States.HEAT
elif diff <= -self.thresholds['HoldCool']:
state_next = States.COOL
else:
state_next = States.HOLD
elif self.state == States.HOLD:
if diff >= self.thresholds['HoldHeat']:
state_next = States.HEAT
self.pid_heat.reset()
elif diff <= -self.thresholds['HoldCool']:
state_next = States.COOL
self.pid_cool.reset()
elif self.state == States.HEAT:
if diff <= -self.thresholds['HeatCool']:
state_next = States.COOL
self.pid_cool.reset()
elif diff <= self.thresholds['HeatHold']:
state_next = States.HOLD
self.pid_hold.reset()
elif self.state == States.COOL:
if diff >= self.thresholds['CoolHeat']:
state_next = States.HEAT
self.pid_heat.reset()
elif diff >= -self.thresholds['CoolHold']:
state_next = States.HOLD
self.pid_hold.reset()
# pid_heat was frozen during COOL (see process_pid()) -
# resume it clean rather than from whatever it last held
# before COOL took over, which by now may be a stale fit
# for a completely different part of the curve.
self.pid_heat.reset()
if state_next != self.state:
self.state = state_next
self.on_state_entered(state_next)