docs: plan HOLD-state pid_heat windup fix from overshoot investigation
Records the root cause of the cold-water overshoot in docs/overshoot.png (integral windup in pid_heat with no anti-windup engagement, since y never saturated) and the refined fix plan: gate pid_heat by FSM state instead of a flat yi_max clamp, which was rejected after the numbers showed it would also cripple legitimate high-rate ramps. Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01KefnwbGDM8CGrhb4sFhVq9
This commit is contained in:
@@ -63,6 +63,22 @@ git history for `temp_controller.py`/`temp_controller_smith.py`).
|
|||||||
before that file was removed entirely — `Pot` dropped `gain`
|
before that file was removed entirely — `Pot` dropped `gain`
|
||||||
entirely, see `components/plant/TODO.md`.
|
entirely, see `components/plant/TODO.md`.
|
||||||
|
|
||||||
|
- [ ] **`pid_heat` can wind up during a `HOLD`-state disturbance with no
|
||||||
|
anti-windup engagement.** A cold-water disturbance while holding drove
|
||||||
|
`pid_heat`'s integral term up without ever saturating `y` (peaked at
|
||||||
|
`y≈0.74` of the `1.0` ceiling), so the existing back-calculation
|
||||||
|
anti-windup (`Pid.process()`, `pid.py:45-48`) never triggered — the FSM
|
||||||
|
never even left `HOLD` (`diff` stayed under `HoldHeat=1.0`). The
|
||||||
|
resulting overshoot took ~35s+ to unwind naturally. A flat `yi_max`
|
||||||
|
clamp was considered and rejected: sustaining a genuine 1.5 K/min ramp
|
||||||
|
needs `y≈0.7-0.75` from `yi` alone at steady state, the same range the
|
||||||
|
disturbance itself peaked at, so no single clamp value can suppress the
|
||||||
|
windup without also capping legitimate ramps. Plan is instead to gate
|
||||||
|
`pid_heat`'s activity by FSM state (frozen/offline while `HOLD`, engaged
|
||||||
|
by command or a new `HoldHeatEngage` threshold) — see
|
||||||
|
`docs/overshoot_hold_windup.md` for the full writeup, open design
|
||||||
|
question (threshold relationship with `HoldHeat`), and test plan.
|
||||||
|
|
||||||
- [ ] **`kalman.py` is now dead code in production.** Neither
|
- [ ] **`kalman.py` is now dead code in production.** Neither
|
||||||
`temp_controller.py` nor `temp_controller_smith.py` uses `Kalman`
|
`temp_controller.py` nor `temp_controller_smith.py` uses `Kalman`
|
||||||
anymore; the only remaining references are
|
anymore; the only remaining references are
|
||||||
|
|||||||
Binary file not shown.
|
After Width: | Height: | Size: 207 KiB |
@@ -0,0 +1,148 @@
|
|||||||
|
# HOLD-state overshoot from a disturbance: root cause and fix plan
|
||||||
|
|
||||||
|
Investigation of the overshoot visible in `docs/overshoot.png`: a cold-water
|
||||||
|
disturbance during a steady HOLD at 30°C caused `theta_ist` to overshoot to
|
||||||
|
~30.5°C and stay there, rather than settling back at soll. This document
|
||||||
|
records the diagnosis and the (not yet implemented) fix plan. Numbers below
|
||||||
|
are pulled from `logs/log_latest.json`.
|
||||||
|
|
||||||
|
## Incident summary
|
||||||
|
|
||||||
|
- Steady HOLD at 30.0°C. Cold water added → `theta_ist` (Smith-corrected)
|
||||||
|
dipped to ~29.49°C (`diff ≈ 0.51°C`).
|
||||||
|
- `diff` never reached `Thresholds.HoldHeat` (1.0°C, `temp_controller_fsm.py`),
|
||||||
|
so **the FSM never left `HOLD`** — the entire episode happened inside what
|
||||||
|
the system still considered "holding".
|
||||||
|
- `pid_hold` (outer loop, `Hold: {kp:0.6, ki:0, kd:0, kt:0}` — pure
|
||||||
|
proportional) tracked `0.6 * max(0, diff)` exactly, tick for tick, peaking
|
||||||
|
at `pid_hold_y ≈ 0.31` — nowhere near its `y_max=1.0` ceiling. Confirmed
|
||||||
|
directly against logged samples: `rate_soll` == `0.6*diff` to the last
|
||||||
|
digit throughout.
|
||||||
|
- `pid_heat` (inner loop, `Heat: {kp:0.08, ki:0.02, kd:0, kt:1.5}`) then
|
||||||
|
chased that `heatrate_soll` target, driving commanded power from a
|
||||||
|
baseline ~500W burst-cycle up to **~2600W** (`y ≈ 0.74` of the 3500W max,
|
||||||
|
see `tasks/heater.py:58-59`: `power = get_power_max() * y`).
|
||||||
|
- Plant dead time (`Td=17s`) and thermal mass (`M=27.96 kg`,
|
||||||
|
`C≈3403 J/(kg·K)`, from `PlantParams` in the log) meant heat from that
|
||||||
|
burst kept arriving after `theta_ist` had already crossed back over soll.
|
||||||
|
By the time `rate_soll` had fallen back to exactly `0` (outer loop asking
|
||||||
|
for zero heat rate), `power_set` was still **1442 W**, decaying only
|
||||||
|
gradually over the next ~35s (1193 → 979 → 817 → 632 → 487 → 337 → 142 W)
|
||||||
|
rather than snapping to 0.
|
||||||
|
- No active cooling actuator exists; the passive loss coefficient
|
||||||
|
(`L=0.2 W/(kg·K)`) gives a time constant `C/L ≈ 17,000s (~4.7h)`, so the
|
||||||
|
resulting ~0.4°C plateau above soll does not visibly decay within any
|
||||||
|
reasonable observation window.
|
||||||
|
|
||||||
|
**Root cause:** `pid_heat`'s integral term (`yi`) accumulated during the
|
||||||
|
~130s the outer loop demanded a real (if modest) heat rate, and nothing
|
||||||
|
bounded that accumulation — the existing anti-windup in `Pid.process()`
|
||||||
|
(`components/pid/pid.py:45-48`) is back-calculation that only corrects `yi`
|
||||||
|
when the combined output `y` is actually clamped at `y_min`/`y_max`. Since
|
||||||
|
`y` peaked at ~0.74, well under the `1.0` ceiling, `awu` was `0` the entire
|
||||||
|
time and the anti-windup mechanism never engaged. The integrator just had to
|
||||||
|
unwind naturally against real (delayed) negative error, which took ~35+
|
||||||
|
seconds after the outer loop had already zeroed its target.
|
||||||
|
|
||||||
|
## Rejected approach: flat `yi_max` clamp on `pid_heat`
|
||||||
|
|
||||||
|
The first fix considered was bounding `yi` directly
|
||||||
|
(`self.yi = max(-yi_max, min(yi_max, self.yi))` in `Pid.process()`,
|
||||||
|
independent of the existing `y`-clamp anti-windup). Numeric check against
|
||||||
|
the real plant model kills this as a standalone fix:
|
||||||
|
|
||||||
|
| scenario | P needed | y needed |
|
||||||
|
|---|---|---|
|
||||||
|
| 1.5 K/min ramp @ 30°C | 2435 W | 0.696 |
|
||||||
|
| 1.5 K/min ramp @ 50°C | 2547 W | 0.728 |
|
||||||
|
| 1.5 K/min ramp @ 66°C | 2636 W | 0.753 |
|
||||||
|
| the actual HOLD disturbance (peak) | 2600 W | 0.74 |
|
||||||
|
|
||||||
|
At steady state (`err=0`), `kp*err` contributes nothing — the entire
|
||||||
|
`y≈0.7-0.75` needed to sustain a genuine 1.5 K/min ramp has to come from
|
||||||
|
`yi` alone, for as long as the ramp lasts. That's the *same* range the
|
||||||
|
disturbance transient itself peaked at. So:
|
||||||
|
|
||||||
|
- `yi_max` set low enough to meaningfully shorten the observed hangover
|
||||||
|
(well under ~0.74, e.g. ~0.3) would permanently cap a real 1.5 K/min ramp
|
||||||
|
far below its commanded rate — not a transient dip, a persistent,
|
||||||
|
uncorrectable shortfall for the entire ramp.
|
||||||
|
- `yi_max` set high enough not to interfere with legitimate ramps (~0.75+)
|
||||||
|
sits at or above what the incident already peaked at, so it never
|
||||||
|
engages and does nothing for the hangover.
|
||||||
|
|
||||||
|
A flat magnitude clamp cannot distinguish "leftover integral from an
|
||||||
|
already-resolved disturbance" from "integral correctly holding up a real
|
||||||
|
ongoing ramp" — in this plant they occupy the same output range. **Rejected.**
|
||||||
|
|
||||||
|
## Refined plan: gate `pid_heat` by FSM state instead
|
||||||
|
|
||||||
|
Bound (or freeze) the *rate* at which `pid_heat` reacts based on FSM state,
|
||||||
|
not a constant on `yi`, since real sustained-rate demand only ever happens
|
||||||
|
in `HEAT`; in `HOLD` any large `yi` is by definition windup, since the
|
||||||
|
target rate there is always ~0 outside of a real disturbance.
|
||||||
|
|
||||||
|
1. **New flag `heat_loop_active`**, scoped to `HOLD` only, in
|
||||||
|
`TempControllerFsm`. `is_holding()` stays `state == HOLD` regardless —
|
||||||
|
Sud step "have we reached target" logic is unaffected.
|
||||||
|
2. **While `heat_loop_active` is False in `HOLD`:** force `y=0`, skip
|
||||||
|
`pid_heat.process()` entirely (freeze it, don't reset — same
|
||||||
|
bumpless-resume convention already used for `HOLD→HEAT`, see
|
||||||
|
`temp_controller_fsm.py:99-101`). `pid_hold` keeps running every tick
|
||||||
|
regardless (it's pure-P, no windup risk, and its output is needed to
|
||||||
|
evaluate the engage condition below).
|
||||||
|
3. **Engagement (`False→True`)**, checked each tick while in `HOLD`:
|
||||||
|
- Explicit command — a new `engage_heat_loop()`/`force_heat()` call,
|
||||||
|
wired to a manual UI action and/or auto-fired from `set_theta_soll()`
|
||||||
|
when the new target is a genuine change (not the same value re-sent
|
||||||
|
every tick).
|
||||||
|
- `diff >= Thresholds.HoldHeatEngage` (new config key).
|
||||||
|
4. **Disengagement:** once `diff` settles back inside the existing
|
||||||
|
`HoldHeat`/`HoldCool` band, held for a short dwell time (a few seconds),
|
||||||
|
to avoid chatter right at the boundary.
|
||||||
|
5. **Config/back-compat:** new threshold merges into `DEFAULT_THRESHOLDS`
|
||||||
|
the same way existing ones do (`temp_controller_base.py:30`).
|
||||||
|
|
||||||
|
### Open design question (unresolved)
|
||||||
|
|
||||||
|
`HoldHeatEngage` needs to sit **below** the existing `HoldHeat`/`HeatHold`
|
||||||
|
FSM threshold (currently `1.0°C`) to ever fire from inside `HOLD` — if
|
||||||
|
`HoldHeat` stays at `1.0`, the FSM fully escalates to `HEAT` (where
|
||||||
|
`pid_heat` always runs anyway) before any larger engage threshold is ever
|
||||||
|
reached. Two ways to resolve, not yet decided:
|
||||||
|
- Raise `HoldHeat`/`HeatHold` too, widening the HOLD↔HEAT band so `HOLD`
|
||||||
|
covers the full deadband and the new flag is the only gate within it.
|
||||||
|
- Keep `HoldHeat` at `1.0`, set the engage threshold below it (e.g.
|
||||||
|
~0.7-0.8°C) — loop only goes offline for small disturbances, engaging
|
||||||
|
before the FSM would escalate to full `HEAT` anyway.
|
||||||
|
|
||||||
|
## Test plan (not yet implemented)
|
||||||
|
|
||||||
|
Stdlib `unittest`, no pytest — `tests/components/pid/test_pid.py`,
|
||||||
|
discoverable via `python -m unittest discover -t . -s tests/components/pid`.
|
||||||
|
|
||||||
|
**A. Unit-level, isolated `Pid`** — no plant involved. Feed a synthetic
|
||||||
|
`err` sequence shaped like the incident (positive `heatrate_err ≈ 0.3` held
|
||||||
|
for ~130 ticks, then decaying/negative tail, matching the real
|
||||||
|
`rate_soll - rate_ist` pulled from the log) into `pid_heat` with the loop
|
||||||
|
gated (frozen while "HOLD"/inactive) vs ungated (today's behavior). Assert:
|
||||||
|
recovery time (ticks after error goes negative until `y` drops back under a
|
||||||
|
small threshold) is measurably shorter when gated; `yi` never grows during
|
||||||
|
the frozen window.
|
||||||
|
|
||||||
|
**B. Closed-loop, self-contained synthetic scenario** — no dependency on
|
||||||
|
the multi-MB log file. Real numbers from `PlantParams`/`config.json`:
|
||||||
|
`Pot(dt)` with `M=27.96, C=3403.43, L=0.2, Td=17`, ambient from
|
||||||
|
`config.json`; `TempController` via `PidFactory.create('Smith', dt)` with
|
||||||
|
the real `Hold`/`Heat`/`Cool` gains. Run closed-loop (controller's own `y`
|
||||||
|
drives the plant, unlike `utils/replay_sim.py`'s open-loop observe-only
|
||||||
|
mode): hold at 30°C until settled, knock `plant.temp` down ~0.5°C to
|
||||||
|
emulate the cold-water event, keep ticking for several minutes. Run twice —
|
||||||
|
gating on vs off — and assert peak overshoot above 30.0°C is measurably
|
||||||
|
smaller with gating, while a separate run driving a genuine 1.5 K/min ramp
|
||||||
|
confirms gating does *not* reduce the sustained ramp rate (guards against
|
||||||
|
reintroducing the flat-clamp regression above).
|
||||||
|
|
||||||
|
## Status
|
||||||
|
|
||||||
|
Plan only — nothing in this document has been implemented yet.
|
||||||