docs: plan HOLD-state pid_heat windup fix from overshoot investigation

Records the root cause of the cold-water overshoot in docs/overshoot.png
(integral windup in pid_heat with no anti-windup engagement, since y never
saturated) and the refined fix plan: gate pid_heat by FSM state instead of
a flat yi_max clamp, which was rejected after the numbers showed it would
also cripple legitimate high-rate ramps.

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01KefnwbGDM8CGrhb4sFhVq9
This commit is contained in:
2026-07-04 12:31:58 +02:00
co-authored by Claude Sonnet 5
parent 8689494be0
commit 13bb011099
3 changed files with 164 additions and 0 deletions
Binary file not shown.

After

Width:  |  Height:  |  Size: 207 KiB

+148
View File
@@ -0,0 +1,148 @@
# HOLD-state overshoot from a disturbance: root cause and fix plan
Investigation of the overshoot visible in `docs/overshoot.png`: a cold-water
disturbance during a steady HOLD at 30°C caused `theta_ist` to overshoot to
~30.5°C and stay there, rather than settling back at soll. This document
records the diagnosis and the (not yet implemented) fix plan. Numbers below
are pulled from `logs/log_latest.json`.
## Incident summary
- Steady HOLD at 30.0°C. Cold water added → `theta_ist` (Smith-corrected)
dipped to ~29.49°C (`diff ≈ 0.51°C`).
- `diff` never reached `Thresholds.HoldHeat` (1.0°C, `temp_controller_fsm.py`),
so **the FSM never left `HOLD`** — the entire episode happened inside what
the system still considered "holding".
- `pid_hold` (outer loop, `Hold: {kp:0.6, ki:0, kd:0, kt:0}` — pure
proportional) tracked `0.6 * max(0, diff)` exactly, tick for tick, peaking
at `pid_hold_y ≈ 0.31` — nowhere near its `y_max=1.0` ceiling. Confirmed
directly against logged samples: `rate_soll` == `0.6*diff` to the last
digit throughout.
- `pid_heat` (inner loop, `Heat: {kp:0.08, ki:0.02, kd:0, kt:1.5}`) then
chased that `heatrate_soll` target, driving commanded power from a
baseline ~500W burst-cycle up to **~2600W** (`y ≈ 0.74` of the 3500W max,
see `tasks/heater.py:58-59`: `power = get_power_max() * y`).
- Plant dead time (`Td=17s`) and thermal mass (`M=27.96 kg`,
`C≈3403 J/(kg·K)`, from `PlantParams` in the log) meant heat from that
burst kept arriving after `theta_ist` had already crossed back over soll.
By the time `rate_soll` had fallen back to exactly `0` (outer loop asking
for zero heat rate), `power_set` was still **1442 W**, decaying only
gradually over the next ~35s (1193 → 979 → 817 → 632 → 487 → 337 → 142 W)
rather than snapping to 0.
- No active cooling actuator exists; the passive loss coefficient
(`L=0.2 W/(kg·K)`) gives a time constant `C/L ≈ 17,000s (~4.7h)`, so the
resulting ~0.4°C plateau above soll does not visibly decay within any
reasonable observation window.
**Root cause:** `pid_heat`'s integral term (`yi`) accumulated during the
~130s the outer loop demanded a real (if modest) heat rate, and nothing
bounded that accumulation — the existing anti-windup in `Pid.process()`
(`components/pid/pid.py:45-48`) is back-calculation that only corrects `yi`
when the combined output `y` is actually clamped at `y_min`/`y_max`. Since
`y` peaked at ~0.74, well under the `1.0` ceiling, `awu` was `0` the entire
time and the anti-windup mechanism never engaged. The integrator just had to
unwind naturally against real (delayed) negative error, which took ~35+
seconds after the outer loop had already zeroed its target.
## Rejected approach: flat `yi_max` clamp on `pid_heat`
The first fix considered was bounding `yi` directly
(`self.yi = max(-yi_max, min(yi_max, self.yi))` in `Pid.process()`,
independent of the existing `y`-clamp anti-windup). Numeric check against
the real plant model kills this as a standalone fix:
| scenario | P needed | y needed |
|---|---|---|
| 1.5 K/min ramp @ 30°C | 2435 W | 0.696 |
| 1.5 K/min ramp @ 50°C | 2547 W | 0.728 |
| 1.5 K/min ramp @ 66°C | 2636 W | 0.753 |
| the actual HOLD disturbance (peak) | 2600 W | 0.74 |
At steady state (`err=0`), `kp*err` contributes nothing — the entire
`y≈0.7-0.75` needed to sustain a genuine 1.5 K/min ramp has to come from
`yi` alone, for as long as the ramp lasts. That's the *same* range the
disturbance transient itself peaked at. So:
- `yi_max` set low enough to meaningfully shorten the observed hangover
(well under ~0.74, e.g. ~0.3) would permanently cap a real 1.5 K/min ramp
far below its commanded rate — not a transient dip, a persistent,
uncorrectable shortfall for the entire ramp.
- `yi_max` set high enough not to interfere with legitimate ramps (~0.75+)
sits at or above what the incident already peaked at, so it never
engages and does nothing for the hangover.
A flat magnitude clamp cannot distinguish "leftover integral from an
already-resolved disturbance" from "integral correctly holding up a real
ongoing ramp" — in this plant they occupy the same output range. **Rejected.**
## Refined plan: gate `pid_heat` by FSM state instead
Bound (or freeze) the *rate* at which `pid_heat` reacts based on FSM state,
not a constant on `yi`, since real sustained-rate demand only ever happens
in `HEAT`; in `HOLD` any large `yi` is by definition windup, since the
target rate there is always ~0 outside of a real disturbance.
1. **New flag `heat_loop_active`**, scoped to `HOLD` only, in
`TempControllerFsm`. `is_holding()` stays `state == HOLD` regardless —
Sud step "have we reached target" logic is unaffected.
2. **While `heat_loop_active` is False in `HOLD`:** force `y=0`, skip
`pid_heat.process()` entirely (freeze it, don't reset — same
bumpless-resume convention already used for `HOLD→HEAT`, see
`temp_controller_fsm.py:99-101`). `pid_hold` keeps running every tick
regardless (it's pure-P, no windup risk, and its output is needed to
evaluate the engage condition below).
3. **Engagement (`False→True`)**, checked each tick while in `HOLD`:
- Explicit command — a new `engage_heat_loop()`/`force_heat()` call,
wired to a manual UI action and/or auto-fired from `set_theta_soll()`
when the new target is a genuine change (not the same value re-sent
every tick).
- `diff >= Thresholds.HoldHeatEngage` (new config key).
4. **Disengagement:** once `diff` settles back inside the existing
`HoldHeat`/`HoldCool` band, held for a short dwell time (a few seconds),
to avoid chatter right at the boundary.
5. **Config/back-compat:** new threshold merges into `DEFAULT_THRESHOLDS`
the same way existing ones do (`temp_controller_base.py:30`).
### Open design question (unresolved)
`HoldHeatEngage` needs to sit **below** the existing `HoldHeat`/`HeatHold`
FSM threshold (currently `1.0°C`) to ever fire from inside `HOLD` — if
`HoldHeat` stays at `1.0`, the FSM fully escalates to `HEAT` (where
`pid_heat` always runs anyway) before any larger engage threshold is ever
reached. Two ways to resolve, not yet decided:
- Raise `HoldHeat`/`HeatHold` too, widening the HOLD↔HEAT band so `HOLD`
covers the full deadband and the new flag is the only gate within it.
- Keep `HoldHeat` at `1.0`, set the engage threshold below it (e.g.
~0.7-0.8°C) — loop only goes offline for small disturbances, engaging
before the FSM would escalate to full `HEAT` anyway.
## Test plan (not yet implemented)
Stdlib `unittest`, no pytest — `tests/components/pid/test_pid.py`,
discoverable via `python -m unittest discover -t . -s tests/components/pid`.
**A. Unit-level, isolated `Pid`** — no plant involved. Feed a synthetic
`err` sequence shaped like the incident (positive `heatrate_err ≈ 0.3` held
for ~130 ticks, then decaying/negative tail, matching the real
`rate_soll - rate_ist` pulled from the log) into `pid_heat` with the loop
gated (frozen while "HOLD"/inactive) vs ungated (today's behavior). Assert:
recovery time (ticks after error goes negative until `y` drops back under a
small threshold) is measurably shorter when gated; `yi` never grows during
the frozen window.
**B. Closed-loop, self-contained synthetic scenario** — no dependency on
the multi-MB log file. Real numbers from `PlantParams`/`config.json`:
`Pot(dt)` with `M=27.96, C=3403.43, L=0.2, Td=17`, ambient from
`config.json`; `TempController` via `PidFactory.create('Smith', dt)` with
the real `Hold`/`Heat`/`Cool` gains. Run closed-loop (controller's own `y`
drives the plant, unlike `utils/replay_sim.py`'s open-loop observe-only
mode): hold at 30°C until settled, knock `plant.temp` down ~0.5°C to
emulate the cold-water event, keep ticking for several minutes. Run twice —
gating on vs off — and assert peak overshoot above 30.0°C is measurably
smaller with gating, while a separate run driving a genuine 1.5 K/min ramp
confirms gating does *not* reduce the sustained ramp rate (guards against
reintroducing the flat-clamp regression above).
## Status
Plan only — nothing in this document has been implemented yet.